Fire Safety Duties for Residential Buildings More Than 11 Metres High
What Regulation 10 of the Fire Safety (England) Regulations 2022 requires for residential buildings more than 11 metres high, and how to check whether a higher or separate regime also applies.
Written for England. Check the position if your property is elsewhere in the UK.
8 min
Key takeaways
- Regulation 10 applies to a qualifying residential building more than 11 metres high, determined using the statutory height and measurement rules, not an approximate storey count
- Communal fire doors must be checked at least every 3 months
- Flat entrance doors must be checked at least every 12 months using best endeavours to gain access
- Wayfinding signage and firefighters' lift/equipment duties are not triggered by this threshold alone - check whether the building is also high-rise (at least 18 metres or at least 7 storeys)
- A building more than 11 metres high using a simultaneous evacuation strategy may also fall within the separate Residential Evacuation Plans Regulations 2025 from 6 April 2026
The More-Than-11-Metres Threshold
Regulation 10 of the Fire Safety (England) Regulations 2022 introduces additional fire-door-check duties for a qualifying residential building more than 11 metres in height. Determine height using the definitions and measurement rules in the applicable legislation rather than an approximate storey count.
What Applies at This Tier
In addition to the duties that apply to all relevant multi-occupied residential buildings (fire-safety instructions to residents and information about fire doors), responsible persons for a qualifying building more than 11 metres high must comply with the following:
What the More-Than-11-Metres Threshold Changes
For a qualifying residential building more than 11 metres high, Regulation 10 requires the responsible person to use best endeavours to check every flat entrance fire door at least every 12 months and to check fire doors in communal areas at least every 3 months.
Fire Door Check Frequency
| Door Location | Check Frequency | Access Requirements |
|---|---|---|
| Common parts (corridors, stairwells) | At least every 3 months | No resident access needed |
| Flat entrance doors | At least every 12 months | Best endeavours to gain access |
Check Whether a Higher or Separate Regime Also Applies
A building that is at least 18 metres high or at least 7 storeys may also be a high-rise residential building for the 2022 Regulations, and is subject to additional requirements concerning plans, external-wall information, a secure information box, wayfinding and firefighters' lifts and essential firefighting equipment.
Separately, from 6 April 2026 a building more than 11 metres high that operates a simultaneous evacuation strategy can fall within the Fire Safety (Residential Evacuation Plans) (England) Regulations 2025, even where it is not high-rise.
Do not use an approximate number of storeys as a substitute for the statutory height/storey tests.
Related guides
- High-rise residential buildings: The 18-metre / 7-storey test and the additional duties it triggers. High-rise residential buildings
- Residential evacuation plans: The separate 2025 regime, including its more-than-11m simultaneous-evacuation test. Residential evacuation plans
Resident Information
As with all relevant multi-occupied buildings, residents of a building more than 11 metres high must also receive the fire-safety instructions and fire-door information required generally under the 2022 Regulations.
Steps to Compliance
- Verify building height: Confirm whether your building exceeds 11 metres using the statutory measurement rules, checking plans or surveying as needed.
- Implement fire door check programme: Establish quarterly checks for common parts and best-endeavours annual checks for flat entrance doors.
- Check whether a higher or separate regime also applies: Determine whether the building meets the 18m/7-storey high-rise test, or the more-than-11m simultaneous-evacuation test under the 2025 Regulations, and apply the additional duties that follow.
- Establish record keeping: Document all checks, access attempts, defects and remedial work.
Additional responsible-person duties in force from 1 October 2023
Section 156 of the Building Safety Act 2022 changed the Fire Safety Order regime in England from 1 October 2023.
A responsible person must now record the fire risk assessment in full and record the fire-safety arrangements, irrespective of the number of employees. Where another person or organisation is engaged to undertake or review the fire risk assessment, record that person's identity or, as applicable, the organisation's identity.
The responsible person must also keep the required responsible-person information current and comply with applicable information-sharing and co-operation duties. This includes taking reasonably practicable steps to identify other responsible persons who share or have duties in respect of the premises and, where relevant, Accountable Persons under the Building Safety Act regime; the relevant parties must exchange the required information and co-operate.
Where responsibility for premises changes, the outgoing responsible person must provide the incoming responsible person with relevant fire-safety information required by the legislation. For buildings containing two or more sets of domestic premises, responsible persons also have additional duties to provide relevant fire-safety information to residents in an understandable form.
These changes were not limited to holiday lets or high-rise residential buildings.
Meeting a recommendation is not automatically compliance
Meeting an individual recommendation does not by itself establish compliance with the Fire Safety Order. Measures must be appropriate to the premises, persons at risk and findings of the suitable and sufficient fire risk assessment.
Frequently Asked Questions
+How do I measure if my building is more than 11 metres?
Measure height using the definitions and measurement rules in the applicable legislation, from ground level to the floor level of the top storey. Do not use an approximate storey count as a substitute for the statutory test - consult your building's plans or a suitably qualified professional if you are unsure.+What if only part of my building is over 11m?
Determine height using the definitions and measurement rules in the applicable legislation. Stepped, mixed-height or otherwise unusual buildings should not be classified using an informal 'any part of the roof' test.+What happens if I don't comply?
The fire and rescue authority can take enforcement action including issuing enforcement notices and prosecuting for serious failures. Non-compliance may also affect insurance and could result in civil liability.+Does this page cover wayfinding signage or lift information?
No. Wayfinding signage and the specific requirements for firefighters' lifts and essential firefighting equipment apply to high-rise residential buildings (at least 18 metres or at least 7 storeys), not merely because a building exceeds 11 metres. See our High-Rise Residential Buildings guide.
Next Steps
Review your current fire door check programme and confirm whether a higher or separate regime also applies to your building.
Sources
- Fire Safety (England) Regulations 2022 — UK Parliament, accessed 2026-09-16
- Fire Safety (Residential Evacuation Plans) (England) Regulations 2025 — UK Parliament, accessed 2026-09-16
- Fire safety in purpose-built blocks of flats — Home Office, accessed 2026-09-16
Need a fire risk assessment?
Tell us about the building and what you need, and we’ll let you know how we can help.

