Fire Door Checks for Blocks of Flats
Guide to fire door inspection requirements for residential buildings in England. Understand the statutory quarterly and annual check frequencies under Regulation 10, and how to assess a door's condition.
Written for England. Check the position if your property is elsewhere in the UK.
9 min
Key takeaways
- Buildings more than 11 metres high must have fire doors in common parts checked at least every 3 months
- Flat entrance doors must be checked at least every 12 months using best endeavours to gain access
- Statutory check frequency, required performance and inspection indicators are three separate things - a fixed gap size or hinge count is not itself a universal statutory rule
- Records of inspections, access attempts, defects and remedial actions must be maintained
- Defects must be assessed and addressed with urgency appropriate to the risk
Fire Door Check Requirements
Under Regulation 10 of the Fire Safety (England) Regulations 2022, responsible persons for residential buildings more than 11 metres high must implement a programme of regular fire door checks. This is a significant requirement, and it is worth separating three distinct things: the statutory check frequency, the performance a door is required to provide, and the technical indicators used to assess that performance during an inspection.
Check Frequency
| Door Type | Location | Minimum Frequency |
|---|---|---|
| Fire doors | Common parts (corridors, stairwells, plant rooms) | At least every 3 months |
| Flat entrance doors | Entrance to each individual flat | At least every 12 months, using best endeavours to gain access |
What to Check
Establish first what performance the particular door is intended to provide and what evidence exists for the doorset or existing construction. Dimensions, hardware and seal requirements are not universal across every historical or proprietary doorset. Compare the door with the building's fire strategy, available certification or manufacturer evidence, applicable current technical guidance and the fire risk assessment. Where the required performance cannot be established, or a defect may compromise it, obtain competent fire-door advice.
Fire Door Inspection Indicators
- Self-closing device: Where a self-closing device is required, verify it closes the door fully into its frame from realistic opening positions.
- Door leaf condition: No holes, damage, distortion or unauthorised alterations that could compromise fire resistance.
- Intumescent strips: Where required for the doorset, present, undamaged and not obstructed by excess paint.
- Smoke seals: Where required for the doorset, intact and correctly fitted around the door edge.
- Gap sizes: Consistent and not excessive for the doorset's design and evidence base - a single fixed measurement does not apply to every door in every building.
- Hinges and ironmongery: Secure, undamaged, and appropriate to the doorset.
- Glazing (if present): Fire-rated glass intact and properly fitted.
- Fire door signage: Appropriate signage, such as "fire door - keep shut", in place where required.
Common Issues Found
- Broken or missing self-closers: The most common defect - door doesn't close automatically.
- Damaged or missing seals: Intumescent strips or smoke seals worn, painted over, or removed, where the doorset requires them.
- Excessive gaps: Gaps too large due to wear, damage, or poor fitting.
- Doors held open without a proper device: Ad hoc wedging defeats the purpose - distinguish this from an approved automatic hold-open or release device.
- Holes or damage: Letter boxes, cables, or damage compromising fire resistance.
Accessing Flat Entrance Doors
Checking flat entrance doors requires access to individual flats. Regulation 10 requires "best endeavours" to carry out these checks, recognising that access cannot always be guaranteed.
Best Endeavours Approach
- Written notice: Give residents advance written notice of planned inspections.
- Multiple appointment options: Offer different times including evenings/weekends if practical.
- Follow-up contact: Send reminders and make additional attempts to arrange access.
- Document all attempts: Keep records of all communication and access attempts.
- Escalate if necessary: If access is consistently refused, document and consider escalation.
Record Keeping
Maintain a clear record of the inspections, access attempts, defects, remedial actions and completion dates so the responsible person can demonstrate and manage compliance. The wider Fire Safety Order recording and management duties also apply as relevant.
What to Record
Date and time of inspection, doors checked and location, findings for each door, any defects identified, action taken or planned, who carried out the inspection.
Dealing with Defects
When defects are found, they must be addressed with urgency appropriate to the risk. A flat entrance door in an occupied dwelling cannot ordinarily be treated like an item of equipment that is simply taken out of service.
Action on Defects
- Critical defects: Door not closing, major damage - assess the seriousness immediately, apply proportionate interim risk controls, and arrange urgent competent repair or replacement.
- Significant defects: Missing seals, poor gaps - repair as soon as reasonably practicable.
- Minor defects: Minor cosmetic damage - schedule for next maintenance cycle.
Additional responsible-person duties in force from 1 October 2023
Section 156 of the Building Safety Act 2022 changed the Fire Safety Order regime in England from 1 October 2023.
A responsible person must now record the fire risk assessment in full and record the fire-safety arrangements, irrespective of the number of employees. Where another person or organisation is engaged to undertake or review the fire risk assessment, record that person's identity or, as applicable, the organisation's identity.
The responsible person must also keep the required responsible-person information current and comply with applicable information-sharing and co-operation duties. This includes taking reasonably practicable steps to identify other responsible persons who share or have duties in respect of the premises and, where relevant, Accountable Persons under the Building Safety Act regime; the relevant parties must exchange the required information and co-operate.
Where responsibility for premises changes, the outgoing responsible person must provide the incoming responsible person with relevant fire-safety information required by the legislation. For buildings containing two or more sets of domestic premises, responsible persons also have additional duties to provide relevant fire-safety information to residents in an understandable form.
These changes were not limited to holiday lets or high-rise residential buildings.
Meeting a recommendation is not automatically compliance
Meeting an individual recommendation does not by itself establish compliance with the Fire Safety Order. Measures must be appropriate to the premises, persons at risk and findings of the suitable and sufficient fire risk assessment.
Frequently Asked Questions
+Who can carry out fire door checks?
Routine visual checks can be carried out by any competent person who has been trained on what to look for. More detailed inspections or remedial work should be done by qualified fire door installers or inspectors.+How much do fire door checks cost?
Costs vary depending on building size and whether you use in-house staff or contractors. Many managing agents train staff to carry out routine checks in-house, with specialist inspection for more detailed assessments.+Do I need to check fire doors if my building is 11 metres or less?
The statutory Regulation 10 frequencies do not apply below the more-than-11-metres threshold, but fire door maintenance is still required under the Fire Safety Order as part of a suitable and sufficient fire risk assessment. Regular checks are good practice for all buildings.
Next Steps
Document your fire door inspection programme as part of your fire risk assessment.