What the 2022 Regulations mean for building managers

Complete guide to the Fire Safety (England) Regulations 2022. Understand the correct all-building, more-than-11-metre and high-rise duties for blocks of flats and multi-occupied residential buildings in England.

Written for England. Check the position if your property is elsewhere in the UK.

14 min

Key takeaways

  • The Fire Safety (England) Regulations 2022 came into force on 23 January 2023 and apply to relevant multi-occupied residential buildings
  • All relevant buildings: provide residents with fire-safety instructions and information about the importance of fire doors
  • More than 11 metres: additionally, best-endeavours annual flat entrance door checks and quarterly communal fire door checks - wayfinding and lift/equipment duties are not triggered by this threshold alone
  • High-rise residential building (at least 18 metres or at least 7 storeys): additionally, secure information box, external-wall information, plans, monthly firefighters' lift/equipment checks and wayfinding signage
  • A separate regime - the Residential Evacuation Plans Regulations 2025 - applies to specified residential buildings from 6 April 2026 and is not part of the 2022 Regulations

Overview

The Fire Safety (England) Regulations 2022 were made under the Regulatory Reform (Fire Safety) Order 2005 framework, using powers inserted by the Fire Safety Act 2021, and came into force on 23 January 2023. They introduce additional duties for responsible persons of multi-occupied residential buildings, on top of the existing requirements of the Fire Safety Order.

Which Buildings Are Affected?

The regulations apply to relevant multi-occupied residential buildings in England - broadly, buildings containing two or more sets of domestic premises (flats) within the scope of the regulations. The specific requirements depend on which category the building falls into, determined using the statutory definitions and measurement rules rather than an approximate storey count.

Additional responsible-person duties in force from 1 October 2023

Section 156 of the Building Safety Act 2022 changed the Fire Safety Order regime in England from 1 October 2023.

A responsible person must now record the fire risk assessment in full and record the fire-safety arrangements, irrespective of the number of employees. Where another person or organisation is engaged to undertake or review the fire risk assessment, record that person's identity or, as applicable, the organisation's identity.

The responsible person must also keep the required responsible-person information current and comply with applicable information-sharing and co-operation duties. This includes taking reasonably practicable steps to identify other responsible persons who share or have duties in respect of the premises and, where relevant, Accountable Persons under the Building Safety Act regime; the relevant parties must exchange the required information and co-operate.

Where responsibility for premises changes, the outgoing responsible person must provide the incoming responsible person with relevant fire-safety information required by the legislation. For buildings containing two or more sets of domestic premises, responsible persons also have additional duties to provide relevant fire-safety information to residents in an understandable form.

These changes were not limited to holiday lets or high-rise residential buildings.

Building Category Matrix

Apply the statutory definitions and measurement rules; do not substitute an approximate storey count for the legal test.
Building categoryStatutory testDuties introduced
Relevant multi-occupied residential buildingContains two or more sets of domestic premises within the regulations' scopeFire-safety instructions to residents; information about the importance of fire doors
More than 11 metres in heightHeight, measured under the statutory rules, exceeds 11 metresPlus: quarterly checks of communal fire doors; best-endeavours checks of flat entrance doors at least every 12 months
High-rise residential buildingAt least 18 metres in height or at least 7 storeys (statutory definitions and measurement rules apply)Plus: secure information box, external-wall information, floor/building plans, monthly checks of firefighters' lifts and essential firefighting equipment (with fault reporting), and wayfinding signage
Specified residential building (separate 2025 regime)High-rise residential buildings, and certain buildings more than 11 metres high using a simultaneous evacuation strategyNot part of these Regulations - see the dedicated Residential Evacuation Plans guide

Duties for All Relevant Multi-Occupied Buildings

Every relevant multi-occupied residential building must provide residents with the prescribed fire-safety instructions and prescribed information about the importance of fire doors. General provision of electronic building information to the fire and rescue service is not an all-building duty under these Regulations - that requirement sits within the high-rise tier below.

  • Fire safety instructions: Provide residents with the prescribed fire-safety instructions and keep them up to date.
  • Information about fire doors: Provide residents with the prescribed information about the importance of fire doors to fire safety.

Section 156 introduced requirements to record responsible-person information and to share specified information with relevant persons and dutyholders. Do not convert this into a universal statutory lobby-display requirement unless another applicable rule specifically requires display.

Additional Duties for Buildings More Than 11 Metres High

For a qualifying residential building more than 11 metres high, Regulation 10 additionally requires the responsible person to check communal fire doors and to use best endeavours to check flat entrance doors, at the frequencies below. Wayfinding signage and the specific high-rise lift and equipment regime are not triggered by exceeding 11 metres alone - they apply only to high-rise residential buildings, described in the next section.

  • Fire door checks - common parts: Check all fire doors in common areas at least every 3 months.
  • Fire door checks - flat entrance doors: Use best endeavours to check all flat entrance doors at least every 12 months.

Additional Duties for High-Rise Residential Buildings (At Least 18m or At Least 7 Storeys)

A high-rise residential building must comply with the relevant requirements for a secure information box, external-wall information, floor/building plans, monthly checks of lifts intended for use by firefighters and essential firefighting equipment, reporting qualifying faults or outages to the fire and rescue service, and wayfinding signage - in addition to the duties that otherwise apply.

  • Secure information box: Install a secure information box for the fire and rescue service containing the required building information.
  • External wall information: Provide information to the fire and rescue service about the materials in external walls.
  • Floor and building plans: Keep up-to-date floor and building plans and provide them to the fire and rescue service electronically.
  • Firefighters' lifts and essential firefighting equipment: Check monthly and report qualifying faults or outages to the fire and rescue service.
  • Wayfinding signage: Install floor identification signage in stairwells to help firefighters and residents orientate themselves.

Residential Evacuation Plans Regulations 2025

From 6 April 2026, the Fire Safety (Residential Evacuation Plans) (England) Regulations 2025 impose additional duties for specified residential buildings, including high-rise residential buildings and certain buildings more than 11 metres high using a simultaneous evacuation strategy. These are not PEEP duties created by the 2022 Regulations - see the dedicated Residential Evacuation Plans guide.

Fire Door Check Requirements

Fire door checks under Regulation 10 are a significant requirement for buildings more than 11 metres high. The responsible person must implement a programme of regular checks:

Fire Door Check Requirements (Regulation 10)

For residential buildings more than 11 metres high: common-parts fire doors checked at least every 3 months; flat entrance doors checked at least every 12 months using best endeavours to gain access. See our Fire Door Checks guide for what to inspect.

Meeting a recommendation is not automatically compliance

Meeting an individual recommendation does not by itself establish compliance with the Fire Safety Order. Measures must be appropriate to the premises, persons at risk and findings of the suitable and sufficient fire risk assessment.

Compliance Timeline and Enforcement

The regulations came into force on 23 January 2023. Fire and rescue authorities enforce them through the existing enforcement regime under the Fire Safety Order. Meeting the requirements described on this page is not, by itself, a complete statement of every duty that may apply - the appropriate precautions also depend on the findings of the fire risk assessment for the particular building.

Frequently Asked Questions

  • +How do I measure my building's height?
    Height is measured using the definitions and measurement rules in the applicable legislation, from ground level to the floor level of the top storey (not the roof). Do not use an approximate storey count as a substitute for the statutory test. If you're unsure, consult your building's plans or seek professional advice.
  • +What if a resident won't let me check their flat entrance door?
    You must use "best endeavours" to check flat entrance doors. This means making genuine attempts to access, such as writing to residents and offering multiple appointment times. If access is refused, document your efforts.
  • +Who enforces these regulations?
    Fire and rescue authorities enforce the regulations using the enforcement regime under the Fire Safety Order 2005. This includes the power to issue enforcement notices, prohibition notices, and prosecute for serious failures.
  • +Do wayfinding signage and lift checks apply to every building more than 11 metres high?
    No. Wayfinding signage and the monthly firefighters' lift and essential firefighting equipment checks apply to high-rise residential buildings - at least 18 metres in height or at least 7 storeys - not merely because a building exceeds 11 metres.

Next Steps

Make sure the fire risk assessment and fire safety arrangements for your building are recorded and up to date.